$50,000 HVAC Install Mistake Required Two Minute Fix
Main summary
Key takeaways
Product/Equipment Reviewed
-
HVAC system at a commercial building
- Multiple York 5-ton package units installed around 2019 (total cooling capacity mentioned: 13 tons).
- Later additions of mini-split systems by Comfort Bros, including a 1.5-ton mini split.
- The claimed outcome of the mini-splits was an increase of cooling by about 4.5 additional tons.
-
Core problem (system-level failure)
- The “product” issue was not a single piece of equipment, but an HVAC setup failure, specifically:
- Wrong thermostat programming (the unit ran in heat mode when cooling was requested).
- The resulting costly corrective actions that followed.
- The “product” issue was not a single piece of equipment, but an HVAC setup failure, specifically:
What Went Wrong (Key Findings)
- A specific package unit (in an office/ducted-to-rafters area) was blowing hot air even though the building was supposed to be cooling for ~6 years.
- The building reportedly was “always hot” and never reached proper cooling, despite regular maintenance visits.
- The eventual diagnosis found:
- The thermostat was not programmed correctly, causing the unit to operate in heat mode when cooling was called for.
- After reprogramming, the building cooled.
Attempts to Fix the Problem (and Comparisons Made)
- Earlier service companies concluded the system was “working fine”, without identifying the root cause.
- After another maintenance company began recommending filter/maintenance, the issue persisted.
- A contractor proposed adding mini splits:
- They claimed the system didn’t have enough BTUs.
- The installation reportedly cost $30k+, including new refrigerant lines, roof penetrations, and electrical circuits.
- The added cooling (+ ~4.5 tons) still did not resolve overheating, because the original control problem remained (the system was effectively still working against cooling).
Main Features / System Behavior Described
- Communicating blowers/motors
- The blower motor was described as bad.
- The blower wheel was seized, and replacement was delayed due to parts availability.
- Economizers
- Economizers are mentioned on the units.
- The reviewer questions whether they were set up correctly.
- Even when it was cooler outside, the compressor was still running.
- Nonstop operation
- Due to the misbehaving unit and ongoing heat loads, the units ended up running continuously.
Pros
- Emergency response and successful repair
- Once the right cause was found and the thermostat was reprogrammed, the space cooled.
- Restoration via parts/replacement
- After blower/motor and related components were replaced, the system was described as working today.
Cons (Major Issues)
- Long-term misdiagnosis / failure to detect
- The system was effectively in a “heating while cooling” condition for 6 years despite multiple maintenance companies.
- Expensive but ineffective “capacity increase”
- Mini-split additions ($30k+) reportedly failed to fix the root cause.
- Potential code/installation quality concerns
- The reviewer states the installation is “not even up to code” (specific code details not provided).
- Higher operating costs and accelerated wear
- With San Diego’s high electric rates, the reviewer estimates electric bills exceeded $10,000, on top of the mini-split cost.
- Continuous operation likely shortened equipment lifespan.
- The reviewer notes communicating motors often fail later than the timeline shown, suggesting unusual stress from sustained runtime.
- Economizer setup questionable
- Possible improper fresh air/economizer configuration may have contributed to unnecessary compressor operation.
User Experience (How It Felt to the Client)
- For years, tenants/owners reported: “It’s always hot.”
- After the correct fix: they were “stoked” the system finally worked—but were unhappy with the amount of money spent to get there.
Overall Cost Impact / Verdict
- Total spend referenced: “$50,000 later” (implied costs include mini splits, energy bills, and service/activity).
- Recommendation (implied by the reviewer):
- Don’t treat the issue as just insufficient BTUs.
- If the system may be misconfigured, verify thermostat controls and operating mode first.
- Verdict:
- The equipment can work correctly once configured, but the diagnosis and service/installation process here was poor and led to unnecessary expense.
- Do not rely on adding capacity as the first solution.
Unique Points Mentioned (Consolidated)
- York package units installed in 2019; building was hot from early on.
- One unit (high duct/rafters) was blowing hot air for ~6 years.
- Multiple companies misdiagnosed the issue; one claimed units were “working fine.”
- Maintenance/filter plan was attempted, but the problem persisted.
- Mini-split addition (~$30k+) included new refrigerant/electrical/roof penetrations.
- Capacity claim: building allegedly needed more BTUs; added ~4.5 tons (and referenced a 1.5-ton mini split).
- Mini splits did not solve the overheating because the root control issue remained.
- Emergency service involved a blower motor failure (bad motor; seized blower wheel; delayed parts).
- Final resolution: thermostat reprogramming, after which the building cooled immediately.
- Units ran nonstop, increasing wear and contributing to motor issues.
- Electric bills estimated > $10,000, plus mini-split costs.
- Reviewer doubts code compliance and questions economizer setup.
- Potentially shortened lifespan due to continuous operation.
- Reviewer observed 20–30 HVAC techs over the years without anyone noticing the real cause until he did.
Different Speaker Contributions
-
Main reviewer/speaker (HVAC tech)
- Provides diagnosis, cost estimates, operational analysis (unit running heat), and critiques of code/installation/economizers and continuous runtime.
-
Building/clients mentioned (owner/staff)
- Report persistent symptoms (“always hot”), mention maintenance plans, and confirm that cooling never happened for 6 years.
-
Other companies/vendors referenced (no separate speaker identified)
- Suggested units were “working fine,” recommended maintenance, and later recommended adding mini splits due to alleged insufficient BTUs.